Many on-orbit noise emission requirements make use of noise criteria (NC) curves
as noise emission limits for individual components, payloads, and racks. NC curves are
well-known standard criteria that are used in building acoustics to describe background
noise associated with mechanical equipment and other self-noise sources found in
unoccupied spaces. Tabulated values of standard NC curves are shown here for reference
only. Please refer to the applicable requirements documents for specific limits and rules
for their application.
Octave band values of Noise Criterion (NC) Curves
| NC Curve |
Octive Band Sound Pressure Level(dB) |
| 63Hz | 125Hz | 250Hz | 500Hz | 1000Hz | 2000Hz | 4000Hz | 8000Hz |
| NC 15 | 47 | 36 | 29 | 22 | 17 | 14 | 12 | 11 |
| NC 20 | 51 | 40 | 33 | 26 | 22 | 19 | 17 | 16 |
| NC 25 | 54 | 44 | 37 | 31 | 27 | 24 | 22 | 21 |
| NC 30 | 57 | 48 | 41 | 35 | 31 | 29 | 28 | 27 |
| NC 35 | 60 | 52 | 45 | 40 | 36 | 34 | 33 | 32 |
| NC 40 | 64 | 56 | 50 | 45 | 41 | 39 | 38 | 37 |
| NC 45 | 67 | 60 | 54 | 49 | 46 | 44 | 43 | 42 |
| NC 50 | 71 | 64 | 58 | 54 | 51 | 49 | 48 | 47 |
| NC 55 | 74 | 67 | 62 | 58 | 56 | 54 | 53 | 52 |
| NC 60 | 77 | 71 | 67 | 63 | 61 | 59 | 58 | 57 |
| NC 65 | 80 | 75 | 71 | 68 | 66 | 64 | 63 | 62 |
|